FCR07DL - reactive power controller

We will be happy to advise you:

FCR07DL - reactive power controller

Power factor controllers FCR05DL and FCR07DL are 4 quadrant controllers designed for low voltage applications. The design gives possibility to control up to 6 compensation stages for FCR05DL and up to 8 stages for FCR07DL regulator. Last output can ...
Power factor controllers FCR05DL and FCR07DL are 4 quadrant controllers designed for low voltage applications. The design gives possibility to control up to 6 compensation stages for FCR05DL and up to 8 stages for FCR07DL regulator. Last output can be programmed to be used as an alarm output or as a normally regulated compensation stage.
show more
zobrazit méně
Order number: FCR07DL

Power factor controllers FCR05DL and FCR07DL are 4 quadrant controllers designed for low voltage applications. The design gives possibility to control up to 6 compensation stages for FCR05DL and up to 8 stages for FCR07DL regulator. Last output can be programmed to be used as an alarm output or as a normally regulated compensation stage.

  • 4 quadrant measurement and regulation
  • designed for LV and MV PFC based on contactors
  • ready for de-compensation reactor usage
  • automatic detection of measuring circuit
  • automatic detection of capacitor steps
  • high sensitivity of current measuring input (2 mA)
  • strong imunity agains high harmonic polution
  • 6 or 8 regulated outputs

Function

Device digitizes measured phase voltage and current in one phase. Then, from those values, parameters like: power factor, effective values of voltage and current, apparent power and reactive power, are calculated. With consideration of requested cosφ it calculated need compensation power. According to its size, regulator switches on or off appropriate capacitor stages.

Within the scope of each power level, regulator uses method of circle switching. All the time connects this stage at appropriate power level which was switched off for longest time. Everything is made so that regulator will reach optimal compensation in one regulation cycle with minimum number of switched stages.

Alarms

Last step of power factor controller is normally working as a standard step but it can be removed from regulation algorithm and used for alarm purposes. Configuration of last step alarm output is easy to be enabled in setup menu.

Circular switching

Within a group of the same powers of capacitor steps, controller uses so called circular switching method. Controller uses the step that was disconnected longest time in order to balance equal usage of all capacitors.

Software

Thanks for software Power Monitor System is possible controllers with RS485 easily configured and also use for monitoring of PFC systems.

    Supply voltage [V] 400 V AC 50 Hz +10%, -20%
    Required power factor 0,8 ind. ÷ 0,8 kap.
    Width [mm] 96
    Depth [mm] 55
    Height [mm] 96
    Weight [g] 650
    Operating temperature -40...+ 70°C
    Panel cutout 91 x 91 mm
    Degree of protection / IP rating IP20
    Current range [A] 0,01 - 5,3
    Number of output channels 6 nebo 8
    Power consumption [VA] 10
    Front panel 97 x 97 mm
    Compensation step value setting ručně / automaticky