HMP - 64M - power consumption controller

HMP - 64M - the controller is designed for monitoring and regulation of electrical energy, or other energy (gas, heat, water, etc.). Regulation is carried out according to the current power, set curve and programmed functions. The device has four ...
HMP - 64M - the controller is designed for monitoring and regulation of electrical energy, or other energy (gas, heat, water, etc.). Regulation is carried out according to the current power, set curve and programmed functions. The device has four inputs and 6 outputs. The outputs consist of 6 switching relay contacts 8A/250V~. The instrument is also equipped with a real-time circuit with backup power supply for approximately 50 hours, and a memory for storing data for 40 days. All data is displayed on a 2x16 character LCD display. There is also a front panel control keypad and LEDs to indicate parallel inputs. The serial interface function is indicated by the RX and TX LEDs.
show more
zobrazit méně

Substitution product

HMP - 164SW- power consumption controller
HMP - 164SW - This controller is a higher version of the HMP 64 controller, it is designed primarily for authorized customers with hourly control mode. The external layout of the controller is the same as the 64 version, but it has a graphic display with the possibility of displaying more variables. In the basic version the controller has 4 inputs and 16 outputs, where 6 outputs are directly on the controller, other commands can be implemented via PM 4 or PM 2 command modules. The number of outputs can be extended up to 40.
HMP - 164SW- power consumption controller
On request
1 609,43 €excl. VAT
Order number: HMP - 64M

Maxima control

Electricity contributes significantly to the operating costs of any business. Hence the increased interest in its efficient use. That is why we offer various types of controllers for monitoring and regulating the reserved capacity. Various expansion modules can be used with the controllers for monitoring, regulation, etc.

The HMP - 64M device is designed to monitor and regulate electrical energy, or other energy (gas, heat, water, etc.). Regulation is carried out in a targeted manner according to the current power output, set curve and programmed functions. The device has four inputs and 6 outputs. The outputs consist of 6 switching relay contacts 8A/250V~.

The instrument is also equipped with a real-time circuit with backup power supply for approximately 50 hours, and a memory for storing data for 40 days. All data is displayed on a 2x16 character LCD display. There is also a front panel control keypad and LEDs to indicate parallel inputs. The serial interface function is indicated by the RX and TX LEDs.

The QERP 16 controller, or slave command modules for monitoring and PCs in the power engineer's office, can be connected via the standard 485 interface. Using the WINREG energy software (software is chargeable), two-way communication with the controller is possible (controller setting, data archiving, monitoring).

Technical data

The controller is equipped with 6 output switching relays 8A/250V~. It has 4 active inputs with inputs 1 to 3 being duplicated on the output optocouplers. The power supply of the active inputs is also derived, it is an unstabilized DC voltage of about 12 to 18 V=. The controller also has an RS 485 interface output and a COM connector for other peripherals.
The real time clock lasts at least 50 hours without power. All data in the controller's memory lasts at least 10 years.
Power supply: 230V~/50Hz
Power consumption: 6 VA
Protection rating IP 20
External dimensions: ModulBOX 9M - 160 x 110 x 60 mm
Weight: 0.5 kg

Basic display

Use the arrows <- -> to switch between the display of the power and work of the main meter ( marked H ) , the sub-meters ( 1 and 2 ) , the estimated work of the main meter at the end of the quarter hour ( O ) and the regulation maximum ( R ). Use the + - to switch between the display of the 1/4 hour time and the actual-real time.
When displaying the regulation maximum ( R ), the value of the monthly increase of the regulation maximum is displayed instead of the time.

Supply voltage [V] 230V~ +5/-10%
Communication interface RS-485
Width [mm] 160
Depth [mm] 60
Height [mm] 110
Weight [g] 500
Operating temperature 0 ... +50 °C
Degree of protection / IP rating IP20
Voltage measurement inputs 4
Number of output channels 6
LCD displej ANO
Power input [VA] 6 VA