1. Safety and proper handling of CT secondaries
    Key idea: A CT secondary with 5 A or 1 A outputs must never be left open when current is flowing through the primary.

  • Short-circuiting the secondary: Yes, the secondary must never remain open under load. If the measuring device is disconnected, always short the CT secondary first.

  • Risks of an open secondary: An open secondary can induce dangerous high voltages, potentially damaging both the CT and the connected instrument.

  • Use of shorting terminals: To ensure safe disconnection and shorting, it is recommended to use terminals with short-circuiting/test blocks.

  • Split-core and clamp-on CTs: The same rules apply to 5 A / 1 A outputs of split-core or clamp-on CTs as to conventional CTs: never leave the secondary open under current, short before disconnecting, and provide single-point grounding.

  1. Grounding of CT secondaries
    Key idea: A CT secondary must always be grounded at one single point to ensure safety and correct operation.

  • Grounding rule: Ground one side of the secondary (usually S2 or terminal l) at a single point in the secondary circuit.

  • Purpose of grounding: This removes capacitive coupling effects and reduces dangerous touch voltages.

  • Emphasis on one point: It is critical that there is only one grounding point along the entire secondary path.

  1. Recommended procedure for installation and maintenance
    Key idea: A standardized procedure minimizes risk and optimizes performance.

  • Location of shorting terminals: Install shorting terminals near the measuring instrument.

  • Disconnecting procedure: When disconnecting an instrument, first close the shorting link and only then disconnect the leads.

  • Grounding location: Ground one side of the secondary (S2/l) at a single point in the switchboard.

  • Route optimization: For shorter runs (up to 2 m using 2.5 mm² conductors), the benefit is clear: line losses (VA) are reduced, and it is easier to remain within the CT’s rated burden.

  1. Calculations and parameters of copper conductors
    Key idea: Correct resistance and loss calculations are essential for proper system dimensioning.

  • Specific resistance of copper:
    • At 0 °C: 0.0178 Ω·mm²/m
    • At 25 °C: 0.020826 Ω·mm²/m

  • Specific conductivity of copper:
    • At 0 °C: 56.18 m/(Ω·mm²)
    • At 25 °C: 48.02 m/(Ω·mm²)

  • Temperature coefficient of copper: 0.0068 K⁻¹

Example (20 m run, 4 mm² cross-section, 5 A current):

  • Resistance: 0.2083 Ω

  • Losses (burden): 5.21 VA

  • Suitable burden range: 5.21 VA (lower 50%) to 9.37 VA (upper 90%)

These guidelines are essential to ensure safe, reliable, and efficient operation of current transformers.